CPO Storage Tank Monitoring System

Automatic Tank Gauge implementation for near-real-time monitoring of CPO storage tanks, covering field instrumentation, data integration, SCADA, commissioning, and operator training.

Timeline / Completed
Engineering RoleIndustrial IoT & SCADA Engineer
Links & Resources
Proprietary / On-Premise
Technology & Hardware Stack
Automatic Tank GaugeRadar SensorHARTModbusIoT GatewayMQTTSCADAThermocouple

Project Overview

Automatic Tank Gauge (ATG) is a system used to monitor the actual condition of CPO storage tanks on a near-real-time basis.

The system displays several key parameters such as level, temperature, density, volume, and CPO stock. This allows operators to obtain information about tank conditions more easily and in a more measurable way.

ATG in this project is not intended to replace manual sounding. ATG readings are used as a reference and are compared with the operator’s manual measurement results.

In addition to current tank conditions, the system provides trend and historical data that can support analysis and audit activities.

From Field Devices to SCADA

One of the interesting parts of this project is how data from field devices is transferred into information that can be used by operators.

The overall system flow consists of several layers:

Radar Sensor
    |
    | HART
    v
HART → Modbus Converter
    |
    | Modbus
    v
IoT Gateway
    |
    | MQTT
    v
Server
    ├── MQTT Broker
    ├── Database
    ├── API / Backend
    ├── Application Server
    ├── Calculation
    └── SCADA

For temperature monitoring:

Thermocouple
    |
    v
Temperature Transmitter
    |
    | Modbus
    v
IoT Gateway
    |
    | MQTT
    v
Server
    |
    v
SCADA

In this architecture, the IoT Gateway functions as the field data acquisition and communication layer. The gateway reads Modbus devices and forwards the data to the server using MQTT.

Calculation is performed on the server based on the data received from the field.

Monitoring the Tank

The system displays:

  • Level — mm and percentage
  • Temperature — individual temperature and average temperature
  • Volume
  • Density
  • Correction Factor
  • CPO Stock
  • Trend
  • Historical Logger

To obtain average temperature, the system uses data from multiple temperature sensors installed in the tank. The calculation considers sensors that are currently immersed in the product so that the average temperature can represent the product condition inside the tank.

Monitoring data is updated at approximately 5-second intervals, allowing operators to observe tank conditions on a near-real-time basis.

My Role in the Project

I was involved from the initial installation stage until the system was ready for use.

My scope of work included:

  • Installation & commissioning
  • Sensor configuration
  • Gateway & communication
  • Data integration
  • Calculation
  • SCADA
  • Fine-tuning
  • Validation
  • Operator training
  • Handover & documentation

Mechanical work was not handled directly by me.

With this scope, I was involved in most of the technical lifecycle of the system, from field devices to the monitoring application.

Installation & Commissioning

One of the main things I paid attention to during installation was safety.

Some work was carried out on top of the storage tank and involved fabricating sensor supports. Because hot work was involved, safety was an important consideration before the work was carried out.

For the radar sensor, one important consideration was sensor leveling. The radar position needs to be properly leveled so that the level reading can work as accurately as possible.

Temperature monitoring uses custom thermocouples with lengths adjusted according to the tank height. The sensors are installed at multiple points so that the system can determine average temperature based on the sensors currently immersed in the product.

After all devices were installed, the process continued with:

Calibration → Fine-Tuning → Comparison → Validation

Comparing ATG with Manual Measurement

An important part of commissioning is comparing ATG readings with manual measurements.

The comparison is performed at the same time to observe the differences between:

  • Radar level
  • Temperature
  • System calculation results

and the manual measurement results.

Differences between ATG and manual measurements can still occur. Therefore, the goal of fine-tuning is not to make both results always identical, but to minimize the difference as much as possible and ensure that the results remain stable.

The project can be considered complete when the comparison results are relatively small, stable, and meet the scope defined in the contract.

Troubleshooting in the Field

During commissioning, several issues required investigation and fine-tuning before the system could be used optimally.

Temperature Reading Fluctuation

One case I encountered was an ATG temperature reading that fluctuated very rapidly.

The changes did not match the actual condition of the product, so I checked the temperature sensor path.

After tracing the connection, a problem was found in the temperature cable connection to the transmitter.

The connection was removed and the sensor cable was connected directly to the transmitter.

After this change, the temperature reading returned to normal.

This simple case became one of the experiences that reminded me that when a reading has a problem, the source of the problem is not always the sensor itself.

Radar Reading vs Manual Sounding

Differences between radar readings and manual sounding are another aspect that needs attention during commissioning.

In one condition, the difference was related to deformation of the tank plate.

Therefore, when a reading difference is found, I do not only look at the sensor data. The physical condition of the tank also needs to be considered, and the result is compared again with the manual measurement.

Calculation Difference

Differences can also occur between ATG calculations and manual results.

One cause that has been found was a mismatch between the tank calibration table used by the ATG system and the manual method.

This taught me that the final monitoring result does not only depend on the sensor, but also on the reference data and calculations used by the system.

Operator Training

After the system completed commissioning and validation, I also conducted operator training.

The training covered:

  • System introduction
  • System topology
  • Sensor operation
  • Data flow
  • SCADA application usage
  • Parameter monitoring
  • Historical data and trends

The goal was not only for operators to be able to use the application, but also to understand in general how the data they see in SCADA originates from field devices.

Result

With the ATG system, operators can more easily monitor storage tank conditions, including:

  • Level
  • Average temperature
  • CPO stock
  • Trend
  • Historical data

Historical data also provides a track record that can support analysis and audit activities.

For head office, the system allows tank conditions to be monitored periodically through the available monitoring platform.

When a condition requires attention, information from the system can serve as one of the references for further checking in the field.

What I Learned

Working from one ATG project to another always gives me new insights.

I not only learned about sensors and data communication, but also developed a better understanding of how a system needs to work from the field level to the monitoring layer.

One of the lessons I remember most is:

“Don’t immediately assume the sensor is broken.”

When a reading is abnormal, there are many things that need to be checked before reaching a conclusion — including wiring, connections, communication, physical device conditions, reference data, and calculations.

Each project brings different problems. From one project to the next, I gain new insights and become more confident in dealing with problems in the field.